Our biogas and sewage gas monitoring solutions support gas flow measurement and process monitoring in renewable energy and wastewater treatment facilities, contributing to stable system operation and effective gas utilization.
Get a Quote →A biogas and sewage gas monitoring solution measures how much gas an anaerobic digester produces, what the gas is made of and how it is handled on the way to engines, boilers, flares or upgrading units. Gas flow meters, gas analyzers, pressure and temperature sensors work together so that operators can follow production, protect equipment and document how much energy is recovered from waste material.
Biogas is wet, can contain hydrogen sulfide and other corrosive traces, and is flammable, which places special demands on instruments. Low line pressure and widely varying flow add further difficulty. Suitable monitoring equipment therefore uses corrosion-resistant parts, tolerates moisture, carries the right hazardous area protection and keeps stable readings at low flow. This page explains the main measurements, technology choices and selection points.
Gas Production Rate
Flow data shows how much gas the digester delivers and is the basis for energy yield reports and process stability checks.
Methane Content
The methane share determines the energy value of the gas and affects engine settings and upgrading performance.
Carbon Dioxide Content
Carbon dioxide levels are tracked alongside methane to understand gas composition and the load on upgrading equipment.
Hydrogen Sulfide
This corrosive and toxic trace gas is monitored to protect engines, pipes and people, and to control desulfurization steps.
Oxygen and Air Ingress
Oxygen readings reveal air leaks or deliberate air dosing, and are a key safety indicator in flammable gas systems.
Pressure, Temperature and Moisture
These values are needed to correct gas volume to reference conditions and to manage condensate in gas lines.
Gas leaves the digester headspace, passes through a holder and conditioning steps, and is then used in an engine, boiler, flare or upgrading unit. Flow and quality measurements are normally placed after conditioning, where the gas is drier and cleaner.
Placing a second flow meter on the flare line shows how much gas is wasted, which is useful for both energy accounting and emissions reporting.
The table gives a general view of common options. Gas composition, moisture and line size usually decide the final choice.
| Technology | Moisture Tolerance | Pressure Loss | Low-Flow Performance | Typical Biogas Use |
|---|---|---|---|---|
| Thermal mass | Moderate | Very low | Very good | Digester output, engine feed |
| Ultrasonic gas | Good | None | Good | Larger pipes, low-pressure lines |
| Vortex | Moderate | Moderate | Limited | Higher flow lines with stable pressure |
| Differential pressure | Good | Moderate | Limited | Large headers, where pressure drop is acceptable |
| Coriolis mass | Moderate | Moderate | Good | Custody or high-accuracy duties |
| Turbine gas meter | Limited | Low | Moderate | Clean, dry gas after treatment |
Because biogas pressure is often only a few millibar above atmospheric, low pressure loss is a decisive requirement, which makes thermal mass and ultrasonic technologies popular choices.
Pressure, temperature and gas composition at the digester show process stability and warn of foaming or overpressure.
Level and pressure readings allow operators to buffer gas, balance production with use and protect the membrane or vessel.
Moisture, hydrogen sulfide and flow data after drying and desulfurization confirm that treatment steps work as intended.
Flow and methane content guide fuel supply, help tune combustion and report energy converted to heat and power.
Flow measurement and flame status confirm safe disposal and document gas that is not used for energy.
Where gas is upgraded to biomethane, composition, flow and pressure data support quality control and billing.
Hydrogen sulfide
Select stainless or coated wetted parts that resist sulfur compounds, and avoid copper alloys in the gas path.
Condensate
Moist gas forms condensate in cold lines, so sensors should be mounted to avoid water collection, with drain points where needed.
Siloxanes and deposits
Sewage gas can carry silicon compounds that leave deposits. Designs with easy cleaning access help preserve accuracy.
Seals and gaskets
Elastomers should be chosen for compatibility with methane-rich, humid gas and the expected temperature range.
Outdoor housings
Plants are exposed to weather and humid air, so enclosures need a suitable ingress rating and corrosion-resistant finish.
Sample systems
Analyzer sample lines should include filters and moisture control so that sensors see conditioned gas.
Recommended Practice
Common Problems
Gas and line data: composition, moisture, temperature, pressure, pipe size and flow range at each point.
Hazardous area rating: required protection type and certificates for the installation zone.
Materials: wetted parts, seals and housings confirmed for wet gas with sulfur compounds.
Interfaces: output signals, communication protocol and totalizer functions for the plant control or energy system.
Service and records: calibration gas needs, maintenance intervals, spare parts and commissioning support.
Tip: A simple process sketch showing gas source, treatment steps and gas users, with each measuring point marked, helps a supplier propose a consistent set of instruments for the whole plant.
Biogas is wet, can contain corrosive traces and often flows at very low pressure and with wide variation. Instruments must offer low pressure loss, good low-flow response and materials that tolerate humid, sulfur-containing gas.
Thermal mass and ultrasonic gas meters are widely used because they create little pressure loss and perform well at low flow. Vortex and differential pressure devices are applied on larger lines where the process allows some pressure drop.
Most plants measure methane, carbon dioxide, oxygen and hydrogen sulfide. Some also track moisture and other trace components, depending on the use of the gas and the requirements of the engine or upgrading plant.
Oxygen in a flammable gas stream can indicate air leakage and creates safety concerns. Monitoring it also helps control any intentional air dosing used for biological desulfurization.
Condensate can wet sensors, cause unstable readings and promote corrosion. Gas drying, slope toward drains and meter locations after conditioning reduce these problems.
Equipment placed in or near zones with flammable gas must carry protection suited to the area classification. Requirements differ by country and site, so state the zone in the enquiry and request the relevant certificates.
Flare metering shows how much gas is not used for energy, supports emissions and energy balance reporting and can reveal problems with engines or upgrading equipment that push gas to the flare.
Pressure and temperature are measured along with flow, and the flow computer or meter converts the reading to a reference condition. Mass-based meters give this result more directly, and moisture should be considered for accurate reporting.
Intervals depend on the sensor type, gas conditions and quality needs. Many sensors need regular checks with calibration gas and replacement after a certain service life, so ask the supplier for guidance based on your gas.
Provide the plant type, gas composition and moisture, line size, pressure and temperature, flow range, zone classification, required analyzer parameters and output signals. A process sketch of the gas line is helpful.